Home » Electronic Measuring Instruments » Data Loggers & Data Acquisition » Data Logger » HIOKI PW3360 Clamp On Power Logger

HIOKI PW3360 Clamp On Power Logger

Portable Energy and Demand Logging for Three-Phase Power

The HIOKI PW3360 is a compact clamp-on power logger for recording energy use, electrical demand and power parameters on single-phase and three-phase circuits.

The PW3360 supports single-phase 2-wire, single-phase 3-wire, three-phase 3-wire and three-phase 4-wire wiring. Its guided QUICK SET function helps with field setup, and measured data can be saved to an SD card or internal memory for energy audits and load studies.

3-Phase, 4-Wire Single- and three-phase circuit measurement
90–780 V Effective AC voltage measurement range
Up to 5 kA Current measurement with compatible clamp sensors
40th Order Harmonic analysis on PW3360-21 only

Two order-code options are available: PW3360-20 is the standard logger, while PW3360-21 adds harmonic voltage, current and power measurements up to the 40th order. The current measurement range depends on the selected clamp sensor.

Use the logger for facility energy audits, equipment load comparisons and tracking changes following energy-saving measures. Current sensors are selected separately; confirm the applicable measurement category, wiring and sensor capacity before deployment.

Multi-Wiring Power Measurement

Supports 1-phase 2-wire, 1-phase 3-wire, 3-phase 3-wire and 3-phase 4-wire systems.

Power and Energy Logging

Records load trends, active power and energy-related values for facility analysis.

Wide AC Measurement Range

Provides a 90–780 V effective voltage measurement range for supported AC circuits.

QUICK SET Guidance

On-screen connection guidance simplifies setup and helps identify wiring errors.

SD and Internal Recording

Stores data to SD media or internal memory for later review and reporting.

Model-Specific Harmonic Analysis

PW3360-21 adds harmonic measurement to the 40th order; PW3360-20 does not include this feature.

Building Energy Audits

Record power demand trends before and after conservation projects.

Three-Phase Distribution Monitoring

Monitor electrical loads on three-phase facility circuits.

Equipment Load Surveys

Measure consumption patterns on production or utility equipment.

Demand Management

Identify periods of high electrical demand from logged results.

Leakage Current Checks

Use a compatible leakage-current clamp sensor for supported leakage-current measurements.

Power System Maintenance

Document changes in circuit loading during maintenance and troubleshooting.

SpecificationPW3360
Model variants PW3360-20; PW3360-21
Measurement wiring Single-phase 2-wire/3-wire; three-phase 3-wire/4-wire
Voltage inputs 3 channels (U1–U3)
Current inputs 3 channels (I1–I3)
Voltage range 600 V AC range; 90–780 V effective measurement range
AC current ranges 500 mA to 5 kA, sensor-dependent
Leakage current ranges 50 mA to 5 A, with compatible leakage clamp sensor
Power range 300 W to 9 MW, depending on wiring and sensors
Basic voltage accuracy ±0.3% rdg. ±0.1% f.s.
Basic current accuracy ±0.3% rdg. ±0.1% f.s. plus sensor accuracy
Active power accuracy ±0.3% rdg. ±0.1% f.s. plus sensor accuracy (power factor = 1)
Harmonics Up to 40th order on PW3360-21 only
Data-save interval 1–30 seconds; 1–60 minutes (14 selections)
Display update 0.5 seconds
Storage SD card or internal memory

Clamp-on current sensors are sold separately. Harmonic analysis is a feature of the PW3360-21 only. Observe the specified electrical safety category and sensor ratings.