BT3554-50 Portable UPS Battery Deterioration Tester

The HIOKI BT3554-50 measures the internal resistance and terminal voltage of stationary batteries to support routine UPS and backup-power maintenance.

Using a 1 kHz AC impedance method, the tester evaluates battery internal resistance without requiring the battery to be removed from its installed host system in typical supported use. Voltage and resistance readings can be assessed together using user-defined comparator thresholds.

With a resistance display range from the 3 mΩ class to the 3 Ω class and DC voltage measurement up to ±60 V, the BT3554-50 is suited to checking individual batteries and compatible low-voltage battery blocks within the instrument’s measurement limits.

1 µΩFinest resistance resolution in 3 mΩ range
±60 V DCMaximum DC voltage measurement range
6,000 RecordsInstrument memory capacity
200 TablesSaved comparator setting tables

Optional Z3210 wireless connectivity enables transfer to supported GENNECT Cross mobile workflows; USB communication is available without that wireless adapter. Use the appropriate compatible test leads and follow the battery maker’s maintenance thresholds.

The base BT3554-50 package is sold without pin-type leads. Select BT3554-51, BT3554-52 or other packages if the required lead is to be bundled.

Simultaneous Resistance / Voltage Checks

Use AC impedance measurement at approximately 1 kHz together with DC voltage to evaluate installed stationary batteries.

Four Resistance Ranges

Choose 3 mΩ, 30 mΩ, 300 mΩ or 3 Ω ranges, with resolution as fine as 1 µΩ.

User-Defined Comparator

PASS, WARNING and FAIL states use thresholds set to suit the battery type, rated capacity and reference condition.

6,000-Record Onboard Memory

Save up to 6,000 readings with linked profile information for repeatable inspection routes and battery tracking.

Optional Wireless Data Transfer

Attach optional Z3210 for supported Bluetooth communication with GENNECT Cross; standard USB connection remains available.

Field-Oriented Inspection Workflow

Auto-hold, auto-memory, record guidance and noise-frequency avoidance help technicians capture consistent maintenance readings.

UPS Battery Maintenance

Check internal resistance and terminal voltage of compatible UPS lead-acid battery strings during planned maintenance.

Data Center Backup Power

Document individual backup battery condition readings for preventive maintenance and replacement planning.

Telecommunications Backup Systems

Track stationary reserve-battery trends for communications sites and related electrical infrastructure.

Industrial Emergency Power

Inspect compatible emergency-power battery systems at facilities and industrial equipment rooms.

Stationary Battery Fleet Records

Store labeled readings and transfer results to a PC or optional mobile workflow for inspection reports.

Battery Replacement Verification

Compare new and in-service battery resistance/voltage values against manufacturer-appropriate baselines and thresholds.

BT3554-50 Basic Specifications

Resistance measurement ranges3 mΩ, 30 mΩ, 300 mΩ, 3 Ω (four ranges)
Resistance range / minimum resolution3 mΩ range: 1 µΩ; 30 mΩ: 10 µΩ; 300 mΩ: 100 µΩ; 3 Ω: 1 mΩ
Resistance accuracy±1.0% rdg ±8 dgt (3 mΩ range); ±0.8% rdg ±6 dgt (other ranges), under specified conditions
Resistance measurement signalApprox. 1 kHz AC; ±30 Hz normal, ±80 Hz with noise-frequency avoidance
DC voltage ranges±6.000 V (1 mV resolution); ±60.00 V (10 mV resolution)
Voltage accuracy±0.08% rdg ±6 dgt, under specified conditions
Maximum rated measurement input60 V DC maximum; AC voltage input not supported
Measurement / response time100 ms measurement time; approximately 1.6 s response time
ComparatorPASS, WARNING, FAIL; 200 saved setting tables
Memory6,000 measurement data sets, arranged as 12 units of 500
CommunicationsUSB standard; Bluetooth with optional Wireless Adapter Z3210
Temperature measurement−10 to 60°C with compatible temperature probe; accuracy depends on probe
Power supply / runtime8 × AA alkaline (LR6) batteries; approximately 8.3 h without Z3210
Dimensions / weight199 × 132 × 60.6 mm (W × H × D) with protector; approximately 960 g including batteries and protector

Accuracy is subject to the manufacturer’s measurement conditions, probes and zero-adjust procedure. The 60 V DC maximum is a rated measurement input limit, not a rating for high-voltage EV battery packs.

Order Codes, Lead Selection and Measurement Scope

BT3554-50: Base tester without a pin-type measurement lead. Suitable HIOKI test leads must be selected separately for the application.

BT3554-51: Package with 9465-10 pin-type lead. BT3554-52: Package with L2020 pin-type lead. Wireless adapter Z3210 is separately available or included in selected higher-tier packages.